Are Compressor Hard Start Devices
Needed?
Compressor hard start devices are a luxury item for service technicians to use
in rectifying a myriad of compressor start problems. It is true that the majority
of hard start device applications result from the marginal voltages delivered
by electric utilities during peak demand periods. As the predominant application
is air conditioning, the hard start device can serve as an insurance policy
for compressor starts when voltages drop to 90% of rated line conditions. The
ability to ensure a compressor start under low voltage conditions can serve
to minimize the number of "nuisance" service calls and allow a service
contractor to focus on true problem events.
As the air conditioning industry has expanded and diversified, numerous types and models of air conditioning units and compressors have entered the marketplace. This diverse proliferation has resulted in the need to provide a one-size-fits-all compressor start device. Investigations recently undertaken by SUPCO indicate that a start device should be closely matched to the compressor, and a one size for all approach may actually cause damage to a compressor if applied incorrectly. All SUPCO technology employs the appropriate safeguards to ensure against compressor damage due to misapplied start devices. This situation does not exist for most other start device manufacturers.
General Function
It is pertinent to discuss the general application and function of a hard start
device. A capacitor in conjunction with a switching device (typically a relay)
is introduced across the start windings of a single-phase compressor. Figure
1. illustrates the typical wiring arrangement for a 2-wire and a 3-wire connection.
When the compressor is called upon to start, the start capacitor provides a voltage boost to the start winding of the motor (effectively simulating the phasor lead/lag of a three-phase motor) and causes the motor rotor to turn. At some point, when the capacitor is released from the start winding, the motor continues to run.
In a 3 wire configuration, the potential relay opens at a manufacturer's specified voltage across the start winding of the motor, effectively removing the start capacitor from the circuit. A third wire is necessary to connect to the run winding. In a 2 wire configuration, the potential relay and start capacitor are connected across the run and start winding. The potential relay opens at a specified increment above line voltage, thus removing the start capacitor from the circuit. There is no need for a third wire.
The size of the capacitor significantly impacts the characteristics of the start winding. Figure 2. shows the generalized impedances for the compressor motor and start devices. As such, the start capacitor should be carefully matched to the specific compressor.
Hard Start Technology
Two main types of start devices exist in the marketplace today. SUPCO has developed
a full range of products in both types to provide a customer with all applicable
choices. Both types have their own desirable applications and each have specific
advantages. The two types of start devices discussed below are
1. PTC - Positive Temperature Coefficient devices
2. Potential Relay devices - voltage sensing and current sensing
PTC Devices
The PTC device has been successfully employed in a number of applications for
many years. SUPCO models SPP, SPP5, SPP6, SPP7S employ PTC technology to ensure
that the start capacitor has dropped from the start circuit after an appropriate
amount of time has elapsed. This device utilizes a ceramic element with a predictable
thermal response to the introduction of electric current. As current is introduced
across the start windings, the PTC element begins to warm. When the PTC device
reaches approximately 250o F (corresponding to 0.6-0.8 seconds), the resistance
in the element increases and creates an open switch that releases the start
winding from the circuit. The 0.6-0.8 seconds that the PTC device allows the
start windings to be engaged is generally enough time to enable the compressor
to start. The advantage of this device is its simplicity. A two-wire connection
between the run and start terminals on the compressor is all that is required
to provide reliable starts in most cases.
However, this device has several
limitations that should be considered if the application is critical.
· The PTC device has no ability to sense whether the compressor has actually
started.
· The amount of time provided for a start boost is dictated solely by
the temperature of the ceramic device, which has warmed due to the introduction
of the starting current.
· If the compressor does not start before the temperature threshold has
been reached, it will not start until the PTC device cycles through a cool-down
period (usually 2 - 3 minutes). Many view this start approach as an appropriate
safety measure. The PTC effectively limits the continued unsuccessful cycling
of the start windings that can often result in a motor burnout. Others will
argue that a start device should be able to re-cycle immediately. If this feature
is desired, a PTC is not the correct start device application.
Potential Relay Devices
The Potential Relay start device has recently been the subject of considerable
attention in the market place. Several manufacturers are promoting products
with a variety of technologies. The primary distinction between the potential
relay devices relates to a voltage sensing or current sensing capability.
The voltage sensing method monitors start winding developed voltage and actuates a mechanical or electronic potential relay to disengage the start capacitor. The electronic potential relay is inherently more reliable and precise than the older type mechanical potential relay. SUPCO employs voltage sensing technology with an electronic potential relay.
The current sensing approach senses current through the run winding and drops the start capacitor out of the circuit based upon a threshold value. Both methods have proven effective in providing devices that are able to "sense" when a compressor has started and thus providing more reliable compressor starts in marginal conditions. However, the current sensing method must employ an internal fuse to protect the motor from potential damage and is more difficult to connect than the 2-wire voltage sensing approach.
Capacitor Size
The proliferation of potential relay type devices has resulted in the notion
that one capacitor can be employed to start all compressors. That is, use the
biggest capacitor and give the compressor a "big kick" to get it started.
The sensing characteristic will drop the capacitor out of the start circuit
when necessary and thus the compressor will not be harmed. This idea, however,
is flawed. The use of a capacitor that is too large for the impedance characteristics
of the windings in some compressors can actually result in significant compressor
damage. Recent investigations indicate that this situation is particularly evident
in voltage sensing devices.
Figure 3. shows a successful compressor start. The run-start and start-common voltages increase to a maximum value and the total supply current drops to operating conditions when the start device is dropped from the circuit. While Figure 4. shows an unsuccessful (locked rotor) compressor start. In this figure, the run-start voltage never increases to a point indicating a motor start. The total supply current remains at a maximum and the motor never starts.


If the start capacitor is too large for the application, the capacitor can actually
mask the developed voltage in the start windings and keep the start capacitor
in the circuit continuously. Figure 5. illustrates a compressor start with a
capacitor that is too large. The motor is actually running, but the run-start
voltage is suppressed below the trigger voltage of the start device. As a result,
the start capacitor remains in the circuit as the motor runs. A secondary, fail-safe
method is necessary to ensure that the start device is ultimately removed from
the circuit. This event can be seen at the end of the time duration of the run-start
current highlighted in Figure 5.
A start device that fails to remove
the start capacitor from the circuit has the potential to cause premature failure
of the start windings in the compressor.
Figure 6 shows the same compressor start using and oversized capacitor without
a safety timing circuit. The run - start voltage is suppressed by the combined
characteristics of the motor windings and the extra large capacitor. It never
reaches the prescribed threshold voltage defined by the potential relay for
removing the start capacitor from the circuit. The total supply current remains
near the locked rotor value even after the motor has started (as highlighted
in Figure 6).

If the capacitor is never removed from the start windings, premature winding failure could occur. As such, care should be taken when selecting capacitor sizes for an application. Care should also be taken regarding products that tout a "bigger capacitor is better" approach to compressor starting. SUPCO E-Class devices provide a secondary timing safety device to ensure that the start capacitor is dropped from the circuit in a fail-safe mode. Figure 5. also shows that the start winding voltage drops appropriately after the start capacitor has been removed in a SUPCO E-Class device.
The E Class Advantage
Compressor start devices are available in a variety of forms. Specific applications
call for specific products. SUPCO is one of very few manufacturers in the marketplace
who provide a complete line of start devices to fit any application. PTC devices
fulfill and will continue to fulfill specific needs in the industry. Potential
relay devices can be found in a wide assortment. Care should be employed in
selecting potential relay devices to ensure that all state-of-the-art developments
are included in the product. The SUPCO E-Class Series comprise the most advanced
developments in start device technology:
1. Voltage sensing technology that
monitors for motor start (current sensing devices require internal fuse protection).
2. A 2-wire connection that simplifies installation
3. A secondary timing circuit that ensures that the capacitor is not permanently
left in the start winding circuit
4. A fully electronic device - minimizing the limitations of mechanical devices
and secondary fusing associated with triac devices
5. A start device matched with an appropriately sized capacitor to cover the
range of compressors for the intended application (one size does not fit all)
The use of compressor start devices
results from a need to ensure that a compressor (usually air conditioning) will
start under voltage conditions that are less than ideal. As discussed, several
options exist in the market to address compressor start concerns. Start devices
exist in many forms for specific applications. SUPCO provides a full range of
products in all relevant technologies to effectively match the proper start
device to the application. Care should be taken to utilize a device that meets
the requirements of the job. Extra caution should be observed when employing
the "one-size-fits-all" and "a bigger capacitor is better"
approach to applying a start device. Consult SUPCO, a manufacturer with a complete
product range, to ensure the greatest success in the start device application.